Seba Teleflex LV Monitor Cable fault location system with monitoring Megger

Code: Seba-KMT Megger Teleflex-LV Monitor


 

Datasheet PDF, 0.8 Mb
 

Description

Teleflex LV Monitor

Cable-monitor and fault location system

 

Benefits

  • Fault location on live low voltage cables
  • 3 phase cable monitor for a permanent check of current and voltage
  • GSM remote controlled system

 

 

Description

The Telefl ex LV Monitor has been designed for the location

of all types of low voltage cable faults but especially the

diffi cult and troublesome intermittent faults. It can be

controlled locally from a portable PC by blue tooth or

remotely over a telephone channel (GSM).

Unlike portable available TDR fault locators, the Telefl ex LV

Monitor is connected simultaneously to all 3 phases of a

live LV cable to allow the local or remote operator to perform

TDR testing on any combination of phases. Power for

the Telefl ex LV Monitor is taken through the 3 phase test

lead and the unit requires at least 1 phase to be energised.

The Telefl ex LV Monitor includes a 4 channel transient

recorder (3 voltages and 1 current) which is used to

acquire information about the exact nature and behaviour

of inter-mittent faults. The signals acquired by the transient

recorder are also used to detect "trigger" conditions for the

TDR system based on voltage distortion and/or overcurrent.

Recordings from 2 units can be used for fault

location by transient travelling waves using a special synchronising

feature.

By providing total control from a remote location the Telefl

ex LV Monitor can be connected to a faulty cable by fi eld

staff who are not necessarily familiar with the analysis of

TDR waveforms - the expertise in adjustment and interpretation

being provided by a centrally located specialist. This

becomes particularly benefi cial when the equipment has to

be left on-site awaiting the (re)-occurrence of an intermittent

fault.

 

Salient features

  • TDR based three phase fault locating system
  • Location of permanent, transient and intermittent faults
  • Application on live low voltage cables
  • Three phase voltage monitor
  • Variable trigger conditions for voltage distortion and/or over current
  • Data storage for 20 events
  • Bluetooth and GSM remote control
  • Easy to use operation software
  • Safe connection with heavy duty fused test leads
 

Standard accessories

Scope of delivery

Telefl ex LV Monitor

3 phase fused test lead, CT clamp, GSM antenna

CD with Software and user manual

 

 

Recommended options

 

 

More products SEBAKMT

SEBA KMT ESG NT PINPOINTING EARTH FAULT LOCATOR IN SHEATH OF UNDERGROUND CABLES

• high accuracy pinpointing of a sheath fault
• Automatic adaptation to voltage level
• Automatic filtration of interfering signals
• Automatic zero calibration, no adjustments necessary
• History mode
• High-contrast color display

 

SEBA KMT VFL CR-20 VERY LOW FREQUENCY CABLE TESTING SYSTEM

• VLF Test System 20 kV
• high test capacity of 3 µF permits the simultaneous testing of all three phases
• method is officially recommended by the two VDE Standards 0276-620 and 0276-621
• VLF is the most economic method for testing PE and XLPE cables

 

SEBA SWG 1750 SURGE WAVE GENERATOR FOR FAULT LOCATION IN CABLES SWG1750 SWG1750C SWG1750CI SWG1750C-4 SWG1750CD

• Voltage Ranges : 0.. 8kV / 0..16kV / 0..32kV
• SWG 1750C with 8 - 16 - 32 kV / 1750 J
• SWG 1750 CI with 8 - 16 - 32 kV / 1750 J, incl. leakage current measurement
• SWG 1750 C-4 with 2 - 4 kV / 1150 J and 8 - 16 - 32 kV / 1750 J
• SWG 1750 CD with 8 - 16 - 32 kV / 3500 J

 

SEBA TELEFLEX VX CABLE REFLECTOMETER FOR FAULT LOCATION SYSTEMS

• Range : 20 m … 1280 km
• Bright and large display
• Easiest operation via self guiding and explaining menus
• ARM Slide Technology
• Automatic storage of all results
• Supports all existing prelocation technologies
• Automatic detection and display of cable end and fault position

 

SEBA KMT HPG 50..80-D DC & AC HIGH VOLTAGE CABLE TESTER

• HPG 50-D, AC testing up to 35 kVRMS/ DC testing up to 100 kV
• HPG 70 / 80-D, AC testing up to 50 / 58 kVRMS / DC testing up to 140 / 150 kV
• Suitable for AC testing and DC testing
• Compact, cast-resin high-voltage transformers
• Separate control and HV-units
• Voltage continuously adjustable
• Powerful system: 1,2 kVA continuous operation, up to 3 kVA 60 min. short-time operation

 

SEBA FAULT SNIFFER FOR DETECTION OF BURNING GASES FROM FAULT CABLES UNDERGROUND

• Customers can stay connected
• Fault location with no supply interrupt
• Reliable avoidance of incorrect excavations
• Fast and easy location of faults
• Can be used on straight or branched networks
• Handy size, easy to transport
• No pre-location required
• Accuracy in the decimetre range
• Sensitive to several specifi c gases and therefore suitable for any insulation material

 

SEBA KMT HPA 100 AC HPA 130 DC BURNDOWN HIGH VOLTAGE TESTING

• Powerful test- and burning system
• Continuous testing with AC voltages up to 100 kVrms at 5 kVA
• Own noise-level below 1 pC
• Built-in overcurrent protection
• DC testing up to 130 kV with optional rectifier

 

SEBA KMT T22/1 AC HIGH VOLTAGE TESTING SYSTEM

• Compact and lightweight
• Continuous testing with AC voltages up to 75 kVrms at 1 kVA
• Expandable with a second transformer for testing up to 150 kVrms
• Built-in overload protection
• DC testing up to 80 kV with optional rectifier

 

SEBA KMT VCAM-5 SEWER PIPELINE VIDEO INSPECTION CAMERA

• One touch recording
• Lightweight and compact design
• Records to USB, SD or HDD
• JPEG still image capture
• Wi-Fi and Ethernet interface

 

SEBA KMT VLOC-9800 LINE LOCATION AND TRACER FOR UNDERGROUND PIPES AND CABLES

• Clearly laid out user interface
• Automatic or manual amplification options
• Depth and amperage at the press of a button
• Distance Sensitive Left/Right GuidanceTM
• Sheath fault location (optional)