MEGGER MPQ2000 Power Energy Quality Analyzer Class-A

Code: MPQ2000 MPQ-2000


 

Datasheet PDF, 5.11 Mb
Datasheet PDF, 2.76 Mb
     

Description

MPQ2000 Portable power quality analyser

About the product
  • Powered off of phase A voltage AC/DC
  • Weatherproof to IP54 standard for use in any environment
  • 1000 VAC and 1500 VDC range
  • Auto CT identifies the current that the instrument is connected to and the range that it is in
  • Connection verification highlights if the product has been connected incorrectly
  • On-board data analysis which can compare results against compliance standards, including setting templates for internal company standards
  • Real time scope and DVM
  • IEC61000-4-30 Class A compliance

The MPQ2000 portable power quality analyser is a highly intuitive, advanced, portable three-phase analyser, delivering unmatched capability, in a rugged IP54 weatherproof enclosure. You can view RMS data, waveforms, demand data, phase angles, harmonics, unbalance, flicker, and more in real time with the MPQ1000 scope mode and DVM mode. When data needs to be recorded, the MPQ2000 record verification will automatically identify the current clamps, recognise their range, and verify the unit is connected properly. This means you can simply connect it and push the record button.

But the hardware is not all it’s about – behind the sturdy exterior is an intelligence that is focused on smart testing, with industry-leading software that enables you to minimise errors while testing, and quickly and easily analyse your results. The MPQ2000 can record for extended periods of time because of its massive memory. It uses an SD card, which makes expanding the memory as easy as simply installing a new SD card. The recorded data can be viewed on the MPQ2000 colour VGA display, or the data can be transferred to the high power Megger PQ Power Quality Analysis software via USB cable, USB drive, Ethernet, or directly from the SD card.

The free software, which requires no license, optimises the MPQ2000 to locate the power quality phenomenon such as lighting issues, computer problems, tripping breakers, and much more. It offers advanced charting, advanced waveform, and advanced harmonic analysis.

User Selectable Power Source:
Power off of Phase A, (AC or DC) power off of
auxiliary power (115/230 AC 50/60Hz) or run off
battery for up to 5 hours!
Indoor and Outdoor operation:
IP54 NEMA4 weatherproof enclosure is designed
for outdoor operation. The unit is robust enough to
remain recording outdoors.
Measures AC and DC Voltage:
up to 1000V (Measure Simultaneously)


4 Voltage Channels (3 Phase and Neutral) and
5 Current Channels (3 Phase, Neutral and Ground
Current) [All voltage channels are isolated]
Auto-identifying, 4 Range flexible current clamps,
powered by the unit. No extra batteries needed.
Configuration Verification: Verifies the connection
is corrent prior to recording. (Supports 13 power
configuration methods)
On Board Scope Mode: Includes Waveform Scope,
Vector Scope and Harmonic Bar Chart Analysis with
Harmonic Direction.

Records PQ parameters on BOTH Voltage and
Current Channels: (Waveform captures for all events
on all channels simultaneously):
Sags / Dips, Swells, Sub-cycle Waveform Distortions,
High Speed Transients (up to 1 µsec), THD, Rapid
Voltage Change (RVC), Mains Signaling Events and
Voltage Phase Shifts. 

APPLICATIONS
  • Using experience gained from supplying a multitude of
  • analyzers to a large number of utilities, industries and
  • service providers, Megger has designed the most versatile
  • unit available today. Some of the applications include the
  • following:
  • Compliance testing to any PQ standard
  • Power factor studies
  • Load studies and load balancing
  • Billing verification
  • Substation monitoring
  • Capacitor bank sizing
  • Transformer analysis and de-rating
  • Motor troubleshooting and inrush testing
  • Switchgear and component failure
  • Tripping breakers
  • Equipment tripping offline
  • Dimming/surging lighting
  • Lamp flicker analysis
  • Neutral overheating

Trends the following parameters: RMS, KW, KVARS, KVA, Displacement
Power Factor (DPF), True Power Factor (TPF), Unbalance,
Frequency, THD, TDD, Harmonics, Inter-Harmonics, Flicker
(PST), Flicker (PLT), Flicker Instantaneous

Automatic Timed Waveform Capture User
programmable to captures period waveform snap
shots on ALL channels simultaneously. Waveforms
are analyzed through the 128th harmonic order.

MPQ2000 FEATURE GUIDE
  • Power off Phase A voltage (90 - 600 V AC/DC)
  • Power from 115 - 240 V (50 Hz/60 Hz)
  • NEMA4 weather-resistant enclosure
  • Differential inputs
  • 4 voltage channels
  • 5 Current channels
  • Fully Class A compliant (IEC61000-4-30 and IEEE1159)
  • 0 to 1000 V ac/dc measurement range
  • RMS voltage and current
  • DC voltage and DC current (requires DC CT)
  • Power parameters (KW, KVAR, KVA, DPF, TPF)
  • Phase angles
  • Energy parameters (KWH, KVARH, KVAH)
  • Voltage dips (sags) and swells
  • Current dips (sags) and swells
  • Transient down to 1 msec
  • IEC unbalance (IEC61000-4-27)
  • ANSII unbalance
  • Total harmonic distortion (THD)
  • Total demand distortion (TDD)
  • Harmonics
  • Inter-harmonics
  • Harmonic direction
  • Main signaling recording
  • IEC flicker (IEC-61000-4-15)
  • Rapid voltage change
  • Phase angle deviation
  • Frequency
  • Auto CT identification
  • Record deviation
  • On-board data analysis
  • On-board scope
  • Real-time harmonics/inter-harmonics bar charts
  • USB communications port
  • Ethernet port
  • USB and SD card support 


Youtube video presentation of MEGGER MPQ2000






 

Standard accessories

ORDERING INFORMATION

Item (Qty) Cat. No.
MPQ2000 9 channel 3-phase
portable power quality analyzer
MPQ2000
*MPQ2000 basic kit MPQ2000-BASIC
*MPQ2000 silver kit MPQ2000-S-KIT
*MPQ2000 silver plus kit MPQ2000-S-KIT-PLUS
*MPQ2000 gold kit MPQ2000-G-KIT
*MPQ2000 gold plus kit MPQ2000-G-KIT-PLUS
*MPQ2000 platinum kit MPQ2000-P-KIT


Included Accessories
Unfused differential voltage lead kit 2007-216
32 GB SD card 90023-619
USB communications cable CA-USB
USB memory stick contains user
guide, Megger PQ PC software and
Megger PQ PC software user guide
1006-532
Ethernet communications cable 36798
Carry Bag Pack 2012-180
Power cord and adapter - US 1007-980
Power cord and adapter - UK 1007-981
Power cord and adapter - EU 1007-982
Battery pack 2008-369

 

Recommended options

Optional Accessories
Green ground lead and clip 2008-101
White jumper lead CA-PA9-JMP-KIT
Fused adapter kit (3 adapters and 3 fuses) 1008-645
Kit of 4 plunger clips 1008-756
Lid modification to include external
Ethernet port
MPQ2000EE

Current Clamps
Four range 6000 A AC rain tight,
self-identifying, flexible rope current
clamps (18 cm ID)
MCCV6000-18
Four range 6000 A AC rain tight,
self-identifying, flexible rope current
clamps (27 cm ID)
MCCV6000-27
Four range 6000 A AC rain tight,
self-identifying, flexible rope current
clamps (37 cm ID)
MCCV6000-37
1000 A AC split core current, selfidentifying current clamps (50 mm ID)
CP-1000WCE-ID
100 A AC split core current, selfidentifying current clamps (20 mm ID)
CP-100CE-ID
20 A AC split core current, selfidentifying current clamps (20 mm ID)
CP-20CE-ID
5 A AC split core current selfidentifying current clamps (20 mm ID)
CP-5CE-ID
AC/DC 600 A split core current selfidentifying current clamps (50 mm ID)
CP-600DC-ID
**Kit of 4 split core self ID 1000A PQ CT CP-1000WCE-ID-KIT
**Kit of 4 split core self ID 100A PQ CT CP-100CE-ID-KIT
**Kit of 4 split core self ID 20A PQ CT CP-20CE-ID-KIT
**Kit of 4 split core self ID 5A PQ CT CP-5CE-ID-KIT
**Kit of 3 split core self ID 600A
(AC/DC) PQ CT
CP-600DC-ID-KIT


GLOSSARY OF TERMS

EFT (Extremely Fast Transient)
Transients that have rise and fall times in the
nanosecond region.

Flicker
An impression of unsteadiness of the visual
sensation, induced by a light stimulus with a
luminance fluctuation over time.


Harmonics
A sinusoidal component of a periodic wave or
quantity having a frequency that is an integral
multiple of the fundamental frequency.


Imbalance
The ratio of the negative sequence component
of a voltage or current to the positive sequence
component of that voltage or current, typically
expressed as a percentage.


Inter-Harmonics
A harmonic component of a periodic quantity
that is not an integer multiple of the fundamental
frequency that the supply system is operating.


IP54
A measurement of environmental protection that
states the ingress of dust is not entirely prevented
but will not enter in sufficient quantity to interfere
with the satisfactory operation of the equipment
and dripping water (vertically falling drops) shall
have no harmful effect.


Phase Angle
The delay between the zero crossing of the
fundamental voltage signal and the fundamental
current signal represented in degrees.


Power Factor
The ratio of the total power input, in watts, to the
total volt-ampere input to the converter.


RMS Current
The root-mean-square value of the current, derived
from the summation of the square root of the
arithmetic mean (average) of the squares of the
original current samples.


RMS Voltage
The root-mean-square value of the voltage, derived from
the summation of the square root of the arithmetic mean
(average) of the squares of the original voltage samples.


RVC (Rapid Voltage Change) A variation of the RMS or peak
value of a voltage between two consecutive levels that is
sustained for a given duration.


Sag/Dip
An instantaneous or momentary decrease in the steady
state RMS value.


Sample
The actual discrete instantaneous measurement the
MPQ2000 performs 256 times per cycle.
Sub-cycle
A power quality event in which the duration is less than
a cycle.


Swell
An instantaneous or momentary increase in the steady
state RMS value.


TDD (Total Demand Distortion)
A measurement of the current THD taking into account
the average current load on the circuit during the
recording interval.


THD (Total Harmonic Distortion)
The ratio of the root-mean-square of the harmonic
content to the root-mean-square value of the
fundamental quantity, expressed as a percent of the
fundamental.


Transient
A sudden non-power frequency change in the steady
state condition of voltage or current.


Waveform Capture
A selection in the MPQ2000 setup file that allows the unit
to record waveforms based on timed intervals. NOTE: the
unit will always capture waveforms when an out-of limitsevent occurs.


 

More products MEGGER

MEGGER IMT100 MULTIFUNCTION INDUSTRIAL TESTER FOR PHOTOVOLTAIC INSTALLATIONS

• Powerful 3-in-1 tester for safe, accurate PV installation
• Exceptionally safe to use
• Complete suite of insulation resistance
• Ready for outdoor conditions

 

MEGGER SMRT33 THREE PHASE RELAY TESTER

• Small, rugged, lightweight and powerful
• Operate with or without a computer
• Intuitive manual operation with Smart Touch View Interface
• High current, high power output - (45 Amps/300 VA rms) per phase
• Network interface provides IEC 61850 test capabilities
• Fully automated testing using AVTS software

 

MEGGER TDR2000/2 TDR CABLE REFLECTOMETER FAULT LOCATOR TDR2000/2RM TDR2000/2R

• 20 km range at VF = 0.90
• Monochrome or colour options
• Primary cell or rechargeable options
• Large back lit LCD Display
• Dual cursor measurement
• Intermittent fault location
• Output pulse amplitude and width control
• Trace Master PC software included
• IP54 Rating
• 2 year Warranty

 

MEGGER DLRO600 DUCTER MICRO-OHMMETER 600A

• Small and weighs less than 33 lbs (15 kg)
• Test currents from 10 A to 600 A dc
• 0.1 µohms best resolution
• On board memory for up to 300 test results and notes
• RS232 port to download stored results or for real time output to a printer
• Supplied complete with 16.4 ft (5 m) test leads and download software

 

MEGGER TM1800 CIRCUIT BREAKER ANALYZER CG-19290 CG-19292 CG-19294 CG-19296

• Modular based design - user configurable TM1800 from nine different modules
• Built in PC with CABA Local software - advanced testing with predefined breaker test plans (templates), onsite measurement view and analysis
• Dual ground testing using DCM module - increased safety with both sides of breaker grounded
• Fast and easy testing - Select-Connect-Inspect workflow and high level user interface
• Graphical results for quick interpretation - timing and motion measurements, coil currents
• USB and Ethernet communication interface - for quick back up, LAN connection and printer options
• CABA Win - for advanced data analysis, database interface and common test data archive

 

CIRCUIT BREAKER TESTER RETROFIT MEGGER ½ DDA1600

• Digital signal processing technology
• Variable firing angle and pulse duration
• Modular, portable design
• Complies with NEMA AB-4 Test Guidelines

 

MICRO-OHMMETER MEGGER MOM600A

• Compact and tough
• Straight forward to use
• 600 A output current

 

MEGGER TDR500/3 TIME DOMAIN REFLECTOMETER & CABLE FAULT LOCATOR 1002-227

• minimum resolution of 0.1 m and a 5 km maximum range
• Simple operation.
• AUTO selection of gain and pulse width.
• Ultra fast pulse for near end fault identification.
• Trace HOLD feature.
• IP54 rating offers real life working.
• Designed for use on all metallic cable pairs.

 

MEGGER MIT2500 2.5KV INSULATION TESTER

• Insulation testing up to 2.5 kV and 200 GΩ range in a handheld instrument
• Guard terminal for high resistance accuracy
• Adjustable insulation test voltage from 50 V to 2500 V
• Stabilised insulation test voltage

 

MEGGER TTR25 TRANSFORMER TURNS RATIO METER, EXCITATION CURRENT, POLARITY

• Fully automatic; fast; easy-to-use; robust; lightweight
• Battery powered
• Tests turns ratio, excitation current, and polarity
• Simple, one-button operation
• Quick-start guide on front panel
• Operator-selectable languages