MEGGER MPQ2000 Power Energy Quality Analyzer Class-A

Code: MPQ2000 MPQ-2000


 

Datasheet PDF, 5.11 Mb
Datasheet PDF, 2.76 Mb
     

Description

MPQ2000 Portable power quality analyser

About the product
  • Powered off of phase A voltage AC/DC
  • Weatherproof to IP54 standard for use in any environment
  • 1000 VAC and 1500 VDC range
  • Auto CT identifies the current that the instrument is connected to and the range that it is in
  • Connection verification highlights if the product has been connected incorrectly
  • On-board data analysis which can compare results against compliance standards, including setting templates for internal company standards
  • Real time scope and DVM
  • IEC61000-4-30 Class A compliance

The MPQ2000 portable power quality analyser is a highly intuitive, advanced, portable three-phase analyser, delivering unmatched capability, in a rugged IP54 weatherproof enclosure. You can view RMS data, waveforms, demand data, phase angles, harmonics, unbalance, flicker, and more in real time with the MPQ1000 scope mode and DVM mode. When data needs to be recorded, the MPQ2000 record verification will automatically identify the current clamps, recognise their range, and verify the unit is connected properly. This means you can simply connect it and push the record button.

But the hardware is not all it’s about – behind the sturdy exterior is an intelligence that is focused on smart testing, with industry-leading software that enables you to minimise errors while testing, and quickly and easily analyse your results. The MPQ2000 can record for extended periods of time because of its massive memory. It uses an SD card, which makes expanding the memory as easy as simply installing a new SD card. The recorded data can be viewed on the MPQ2000 colour VGA display, or the data can be transferred to the high power Megger PQ Power Quality Analysis software via USB cable, USB drive, Ethernet, or directly from the SD card.

The free software, which requires no license, optimises the MPQ2000 to locate the power quality phenomenon such as lighting issues, computer problems, tripping breakers, and much more. It offers advanced charting, advanced waveform, and advanced harmonic analysis.

User Selectable Power Source:
Power off of Phase A, (AC or DC) power off of
auxiliary power (115/230 AC 50/60Hz) or run off
battery for up to 5 hours!
Indoor and Outdoor operation:
IP54 NEMA4 weatherproof enclosure is designed
for outdoor operation. The unit is robust enough to
remain recording outdoors.
Measures AC and DC Voltage:
up to 1000V (Measure Simultaneously)


4 Voltage Channels (3 Phase and Neutral) and
5 Current Channels (3 Phase, Neutral and Ground
Current) [All voltage channels are isolated]
Auto-identifying, 4 Range flexible current clamps,
powered by the unit. No extra batteries needed.
Configuration Verification: Verifies the connection
is corrent prior to recording. (Supports 13 power
configuration methods)
On Board Scope Mode: Includes Waveform Scope,
Vector Scope and Harmonic Bar Chart Analysis with
Harmonic Direction.

Records PQ parameters on BOTH Voltage and
Current Channels: (Waveform captures for all events
on all channels simultaneously):
Sags / Dips, Swells, Sub-cycle Waveform Distortions,
High Speed Transients (up to 1 µsec), THD, Rapid
Voltage Change (RVC), Mains Signaling Events and
Voltage Phase Shifts. 

APPLICATIONS
  • Using experience gained from supplying a multitude of
  • analyzers to a large number of utilities, industries and
  • service providers, Megger has designed the most versatile
  • unit available today. Some of the applications include the
  • following:
  • Compliance testing to any PQ standard
  • Power factor studies
  • Load studies and load balancing
  • Billing verification
  • Substation monitoring
  • Capacitor bank sizing
  • Transformer analysis and de-rating
  • Motor troubleshooting and inrush testing
  • Switchgear and component failure
  • Tripping breakers
  • Equipment tripping offline
  • Dimming/surging lighting
  • Lamp flicker analysis
  • Neutral overheating

Trends the following parameters: RMS, KW, KVARS, KVA, Displacement
Power Factor (DPF), True Power Factor (TPF), Unbalance,
Frequency, THD, TDD, Harmonics, Inter-Harmonics, Flicker
(PST), Flicker (PLT), Flicker Instantaneous

Automatic Timed Waveform Capture User
programmable to captures period waveform snap
shots on ALL channels simultaneously. Waveforms
are analyzed through the 128th harmonic order.

MPQ2000 FEATURE GUIDE
  • Power off Phase A voltage (90 - 600 V AC/DC)
  • Power from 115 - 240 V (50 Hz/60 Hz)
  • NEMA4 weather-resistant enclosure
  • Differential inputs
  • 4 voltage channels
  • 5 Current channels
  • Fully Class A compliant (IEC61000-4-30 and IEEE1159)
  • 0 to 1000 V ac/dc measurement range
  • RMS voltage and current
  • DC voltage and DC current (requires DC CT)
  • Power parameters (KW, KVAR, KVA, DPF, TPF)
  • Phase angles
  • Energy parameters (KWH, KVARH, KVAH)
  • Voltage dips (sags) and swells
  • Current dips (sags) and swells
  • Transient down to 1 msec
  • IEC unbalance (IEC61000-4-27)
  • ANSII unbalance
  • Total harmonic distortion (THD)
  • Total demand distortion (TDD)
  • Harmonics
  • Inter-harmonics
  • Harmonic direction
  • Main signaling recording
  • IEC flicker (IEC-61000-4-15)
  • Rapid voltage change
  • Phase angle deviation
  • Frequency
  • Auto CT identification
  • Record deviation
  • On-board data analysis
  • On-board scope
  • Real-time harmonics/inter-harmonics bar charts
  • USB communications port
  • Ethernet port
  • USB and SD card support 


Youtube video presentation of MEGGER MPQ2000






 

Standard accessories

ORDERING INFORMATION

Item (Qty) Cat. No.
MPQ2000 9 channel 3-phase
portable power quality analyzer
MPQ2000
*MPQ2000 basic kit MPQ2000-BASIC
*MPQ2000 silver kit MPQ2000-S-KIT
*MPQ2000 silver plus kit MPQ2000-S-KIT-PLUS
*MPQ2000 gold kit MPQ2000-G-KIT
*MPQ2000 gold plus kit MPQ2000-G-KIT-PLUS
*MPQ2000 platinum kit MPQ2000-P-KIT


Included Accessories
Unfused differential voltage lead kit 2007-216
32 GB SD card 90023-619
USB communications cable CA-USB
USB memory stick contains user
guide, Megger PQ PC software and
Megger PQ PC software user guide
1006-532
Ethernet communications cable 36798
Carry Bag Pack 2012-180
Power cord and adapter - US 1007-980
Power cord and adapter - UK 1007-981
Power cord and adapter - EU 1007-982
Battery pack 2008-369

 

Recommended options

Optional Accessories
Green ground lead and clip 2008-101
White jumper lead CA-PA9-JMP-KIT
Fused adapter kit (3 adapters and 3 fuses) 1008-645
Kit of 4 plunger clips 1008-756
Lid modification to include external
Ethernet port
MPQ2000EE

Current Clamps
Four range 6000 A AC rain tight,
self-identifying, flexible rope current
clamps (18 cm ID)
MCCV6000-18
Four range 6000 A AC rain tight,
self-identifying, flexible rope current
clamps (27 cm ID)
MCCV6000-27
Four range 6000 A AC rain tight,
self-identifying, flexible rope current
clamps (37 cm ID)
MCCV6000-37
1000 A AC split core current, selfidentifying current clamps (50 mm ID)
CP-1000WCE-ID
100 A AC split core current, selfidentifying current clamps (20 mm ID)
CP-100CE-ID
20 A AC split core current, selfidentifying current clamps (20 mm ID)
CP-20CE-ID
5 A AC split core current selfidentifying current clamps (20 mm ID)
CP-5CE-ID
AC/DC 600 A split core current selfidentifying current clamps (50 mm ID)
CP-600DC-ID
**Kit of 4 split core self ID 1000A PQ CT CP-1000WCE-ID-KIT
**Kit of 4 split core self ID 100A PQ CT CP-100CE-ID-KIT
**Kit of 4 split core self ID 20A PQ CT CP-20CE-ID-KIT
**Kit of 4 split core self ID 5A PQ CT CP-5CE-ID-KIT
**Kit of 3 split core self ID 600A
(AC/DC) PQ CT
CP-600DC-ID-KIT


GLOSSARY OF TERMS

EFT (Extremely Fast Transient)
Transients that have rise and fall times in the
nanosecond region.

Flicker
An impression of unsteadiness of the visual
sensation, induced by a light stimulus with a
luminance fluctuation over time.


Harmonics
A sinusoidal component of a periodic wave or
quantity having a frequency that is an integral
multiple of the fundamental frequency.


Imbalance
The ratio of the negative sequence component
of a voltage or current to the positive sequence
component of that voltage or current, typically
expressed as a percentage.


Inter-Harmonics
A harmonic component of a periodic quantity
that is not an integer multiple of the fundamental
frequency that the supply system is operating.


IP54
A measurement of environmental protection that
states the ingress of dust is not entirely prevented
but will not enter in sufficient quantity to interfere
with the satisfactory operation of the equipment
and dripping water (vertically falling drops) shall
have no harmful effect.


Phase Angle
The delay between the zero crossing of the
fundamental voltage signal and the fundamental
current signal represented in degrees.


Power Factor
The ratio of the total power input, in watts, to the
total volt-ampere input to the converter.


RMS Current
The root-mean-square value of the current, derived
from the summation of the square root of the
arithmetic mean (average) of the squares of the
original current samples.


RMS Voltage
The root-mean-square value of the voltage, derived from
the summation of the square root of the arithmetic mean
(average) of the squares of the original voltage samples.


RVC (Rapid Voltage Change) A variation of the RMS or peak
value of a voltage between two consecutive levels that is
sustained for a given duration.


Sag/Dip
An instantaneous or momentary decrease in the steady
state RMS value.


Sample
The actual discrete instantaneous measurement the
MPQ2000 performs 256 times per cycle.
Sub-cycle
A power quality event in which the duration is less than
a cycle.


Swell
An instantaneous or momentary increase in the steady
state RMS value.


TDD (Total Demand Distortion)
A measurement of the current THD taking into account
the average current load on the circuit during the
recording interval.


THD (Total Harmonic Distortion)
The ratio of the root-mean-square of the harmonic
content to the root-mean-square value of the
fundamental quantity, expressed as a percent of the
fundamental.


Transient
A sudden non-power frequency change in the steady
state condition of voltage or current.


Waveform Capture
A selection in the MPQ2000 setup file that allows the unit
to record waveforms based on timed intervals. NOTE: the
unit will always capture waveforms when an out-of limitsevent occurs.


 

More products MEGGER

MEGGER DET14C 1000-761 DET24C 1000-762 EARTH RESISTANCE CLAMP METER

• Elliptical clamp shape improves access to earth cables and straps up to 50 mm
• Low maintenance flat jaw interface
• Measures ground resistance from 0.05 O to 1500 O
• Measures true RMS ground leakage current from 0.5 mA rms to 35 A rms
• CAT IV 600 V safety rating
• Backlit LCD display

 

MEGGER S1-1568/2 EXPERT 15KV INSULATION RESISTANCE MEGOHMMETER

• Reliable results in noisy substations
• Accurate testing with RE>Act™
• Remote control for safer, easier testing
• PI Predictor™ cuts test time in half
• Full diagnostic suite with PDC capability

 

MEGGER PAT120 PAT150 PAT150 ELECTRICAL INSTALLATIONS TESTER FOR CONTINUITY, INSULATION, LEAKAGE AND TOUCH CURRENT TEST

• Simple tick or cross, pass or fail indication plus measurement
• Tough, rubber armoured with built-in front cover, hardened, scratch-proof display window
• Includes 250 V insulation and leakage testing for safe IT testing and surge protected devices
• Testing portable and fixed electrical equipment
• 10 mA and 30 mA portable RCD lead testing (PAT150)
• Adjustable PASS test limits (PAT150)
• Substitute and mains powered leakage testing (PAT150)

 

MEGGER TTR100 TRANSFORMER TURNS RATIO METER, PHASE DISPLACEMENT, VECTOR GROUP, POLARITY

• Tests turns ratio, phase displacement, excitation current, vector group, winding resistance and polarity
• Fully automatic; fast; easy-to-use; handheld; robust; lightweight
• Battery powered with power-saving and shutdown function
• Alphanumeric keyboard
• RS232 for data transfer and printing
• Stores 200 test results and 100 user-defined transformer test settings

 

BOND TESTER MEGGER - BT51

• High test current
• Four terminal measurement
• Two measuring ranges (2000 mO. and 20,00 mO.)and maximum resolution of 0,01 mO.
• Protected against inadvertent connection to the mains supply

 

MEGGER FREJA 300 PROGRAMMA RELAY TESTER CF-19091

• can generate 4x150 V (82 VA) and 3x15 A (87 VA) or 1x45 A (250 VA).
• Manual and automatic control
• Easy to use
• Excellent software provides great visuals and simple setup
• Lightweight and portable
• Highly accurate
• User can calibrate unit

 

MEGGER EGIL BREAKER ANALYZER BM-19090 BM-19093 BM-19095

• Suitable for testing timing and travel on all circuit breakers with single interrupter per phase
• Extremely easy-to-use and reliable
• Two separate timing channels for measurement of auxiliary contacts
• Analog measurement channels for travel transducers or general voltage/current measurements
• Static and dynamic resistance measurements along with the SDRM201 accessory

 

MEGGER TORKEL 820 BS-49092 TELECOM BATTERY LOAD DISCHARGE TESTER PROGRAMMA

• Combines efficiency with portability
• Batteries can be tested "in service"
• Discharge 24 and 48 V batteries at a current of 270 A
• 12 V batteries at 135 A
• Two or more TORKEL 820 units and/or extra load units TXL, can be linked together if you need higher current.

 

SINGLE PHASE HAND CRANKED TRANSFORMER TURNS RATIO TESTER MEGGER - TTR550005B

• Used for testing single phase power and distribution transformers
• Design based on precision bridge measuring technique
• Unmatched accuracy (½0.1%) in a portable design

 

MEGGER SMRT410 RELAY TEST SYSTEM

• Small, rugged, lightweight and powerful
• Operates with or without a computer
• Intuitive manual operation with Smart Touch View Interface
• High current, high power output (60 Amps/300 VA rms) per phase
• Flexible output design provides up to 4-phase voltage and up to 10-phase current
• Network interface provides IEC 61850 test capabilities
• Fully automated testing using AVTS software