Digital Insulation Megohmmeter 5kV Chauvin Arnoux CA6549

Code: Chauvin Arnoux CA6549


 

Datasheet PDF, 0.72 Mb

Description

In its site-adapted casing, the C.A 6549 insulation tester offers quantitative and qualitative insulation analysis, on a large backlit graphic screen!

 

 

  • measurement range: 10k? to 10T?!
  • 4 fixed test voltages: 500 / 1,000 / 2,500 and 5,000V
  • adjustable test voltage position: 40 to 5,100V in 10V or 100V increments
  • step voltage mode: R(Utest) measurement curve viewed on the screen and gradient calculated automatically in ppm/V
  • DAR, PI and DD quality ratios calculated automatically
  • programmable test length and R(t) measurement curve displayed directly on the screen
  • with indication of measurement t° after measurement, resistance recalculated to reference temperature for reliable and accurate insulation monitoring
  • many other functions: test voltage locking, smooth function, programmable alarms, etc.
  • can record thousands of measurements
  • RS 232 connector for connection to PC or very compact serial printer
  • power supply: rechargeable NiMH battery for 30 days' operating with 10 DAR measurements and 5 PI measurements per day
  • electrical safety: IEC 61010-1 Cat.III 1,000V or Cat.I 2,500V and 61557
  • dimensions: 270x250x180mm; mass: 4.3kg

 

 

 

Standard accessories

C.A 6547 Megohmmeter .................................... P01139702

C.A 6549 Megohmmeter .................................... P01139703

Delivered with a carrying bag containing:

½ 2 safety leads 3 m long with HV plug and HV crocodile clip (red/blue)

½ 1 guarded safety plug 3 m long with an HV plug with rear connection

and an HV crocodile clip (black)

½ 1 lead with rear connection (blue) 0.35 m long

½ 1 mains power cable 2 m long,

½ 1 communication lead,

½ 1 simplified operating manual

½ 1 operating manual in 5 languages

 

More products CHAUVIN ARNOUX

ELECTRICAL INSTALLATION TESTER CHAUVIN ARNOUX CA6114

• automatic installation status test immediately after connection
• measurement of voltage (10 to 440V AC/DC) and frequency (15.3 to 450Hz)
• installation insulation measurement at 500V
• standard earth connection resistance measurement (1 stake + loop method)
• PE conductor continuity test
• measurement of internal loops
• testing of RCDs up to 500mA (exact tripping time and current)
• phase rotation testing

 

EARTHING RESISTANCE TESTER CHAUVIN ARNOUX CA6471

• extensive measurement ranges: 0.001? to 100 k?
• adjustment of the measurement frequency between 41 Hz and 512 Hz
• 10 times greater accuracy due to its 4-pole measurement method
• measuring soil resistivity
• calculate r automatically by the Wenner or Schlumberger methods
• Ergonomic, comprehensive and accurate

 

SOLAR PANEL EFFICIENCY TESTER CHAUVIN ARNOUX FTV100 GREENTEST

• electrical power survey
• Calculation of solar panel efficiency
• Calculation of inverter efficiency
• Voltage up to 1,000 VDC / 600 VAC
• Current up to 1,400 ADC / 3,000 AAC
• AC/DC power: 20,000 WDC / 1,200 WAC

 

EARTH GROUND RESISTANCE TESTER ON PYLONS CHAUVIN ARNOUX CA6472

• 5 tools in 1 with this tester
• extensive measurement ranges: 0.001?to 100 k?
• analysing the frequency behaviour of the earthing systems (from 41 Hz to 5 kHz)
• high-level, expert calculation capabilities
• IP 53 leakproofing

 

THREE-PHASE ENERGY QUALITY ANALYZER CHAUVIN-ARNOUX CA8334B QUALISTAR

• Complete three-phase analysis:
• - voltage, current,
• - power / energy,
• - harmonics (up to 50th order), flicker,
• - measurement of transients,
• - alarm trigger...
• Processing of data via PC software QualistarView or DataViewer Pro.
• Recording of 12 screens
• Compliant with IEC 61010-1, 600V Cat.IV

 

ANALOGUE MEGOHMMETER 1000V CHAUVIN ARNOUX CA6513

• insulation: up to 1,000MO (1 cal.) at 500V and 1,000V DC
• AC voltage: 0 to 600V
• resistance: 0 to 1,000O
• continuity: -10O to +10O (I=200mA)
• automatic testing of voltage absence by direct measurement


RCD TESTER CHAUVIN ARNOUX CA6030

• Direct, safe connection to installation mains
• Automatic installation voltage and frequency measurement
• Tests standard, selective, A and AC RCDs
• 5 fixed calibres 10/30/100/300/500mA + 1 calibre adjustable from 6 to 650mA
• Checks RCD trips / trip time measurement (pulse or ramp mode) and exact trip current (ramp mode)

 

EARTH AND LOOP RESISTANCE TESTER CHAUVIN ARNOUX CA6456

• loop resistance and impedance: L-N, L-L, and L-PE from 0.20 to 4 kO
• short-circuit current displayed up to 40 kA by calculation (Uref/ZL-PE)
• clamp measurement of current and leakage current (option)
• Cat. III, 600V

 

DIGITAL INSULATION MEGOHMMETER 500V CHAUVIN ARNOUX CA6521

• insulation: up to 2G? at 250V and 500V DC
• voltage indication before insulation measurement: 0 to 600V AC/DC (blocking if U>25V)
• continuity: -20? to +20? (audible beep)
• giant 400-count display + bargraph (simultaneous reading of measurement and analogue variance)
• back stand for use on a table or on the ground
• long battery life: 6 x 1.5V batteries


MEGOHMMETER 15KV CHAUVIN ARNOUX CA6555

• Wide measurement range from 10 kohm to 30 Tohm
• Fixed or programmable test voltage from 40V to 15 kV
• 5mA max. charging current
• Large backlit LCD screen with digital display, bargraph and R(t)+u(t), i(t) and i(u) graphs
• Automatic ratio calculation: DAR / PI / DD / DR (ppm/V)
• Multiple test modes: voltage ramp and step with "burning", "early break" and "I-limit" modes