One instrument for all electrical safety tests and Power Quality analysis
GSC60 was designed with the aim of making safety of electrical installations visible and valuable, easily and quickly.
Thanks to the new HTOS™ system the unit displays a message OK - NOT OK after completing the test.
The user interface, totally updated under HTOS™, permits to set and carry out measurements in few steps.
You can store all recorded data and create folders and subfolders for each kind of test adding comments and notes by means of virtual keyboard.
GSC60 is also a three-phase power and energy consumption analyzer boasting, as unique feature, its FREE APP HTAnalysis compatible with iOS and Android.
Test results can be transferred through Wi-Fi onto smartphone or tablet enclosing a picture, a video or a voice note to each measurement. You can transfer everything onto HT Cloud and make data available in real time for your colleagues all over the world.
GSC60 makes the job of installer, electrician or consultant easy, rapid and cost-effective.
HTOS™Control the Power.
Get access through touchscreen to your measurement. Quickly set measurement parameters and press GO. Here it is, HTOS™, designed to make your work easier. Its’ result options OK and NOT OK as well as its Help OnLine will make it your best partner and save you time.
Evolution of saving.
Virtual keyboard to enter comments
Saving on file structure
New detailed reports with TopView software
Electrical safety measurements
AUTO Function to work easier.
Rapid setting of limit values and test voltages
through virtual keyboard
Setting of Timer for the test where is available.
Earth Resistance
Earth resistance with 2- or 3-pole volt-ampere method in TT, TN and IT systems.
Soil resistivity with 4-pole Wenner method.
Stackless earth ground resistance measurement with T2100
Non-trip earth loop impedance measurement
Power Quality and energy analysis
9 types of electrical systems available.
632 parameters can be recorded for over two months.
Real-time display of all waveforms, harmonics, vector diagrams as well as summary function on phases for a quick reading of the most important parameters.
Detection of voltage anomalies with a resolution of 20ms.
Measures and record the electrical absorption of all the equipment connected to the main power supply.
Full Batteries at All Times.
GSC60 is so compact that a new power technology had to be designed to charge batteries.
You just need to power the unit and it will charge the batteries.
Or you can always start working by simply replacing them with standard AA batteries.
All in real time!
Wi-Fi connection allows you to display on your tablet/smartphone/PC in real time:
Waveforms
Vector Diagrams
Harmonics
All parameters of each phase
Zoom, Zoom, Zoom! Enlarge, Jump, Analyze. Two finger needed.
With HTAnalysis™ you can:
Analyze the full recording on your device
Compare up to 16 quantities at the same time Immediately analyze
events like voltage dips and peaks
Use the JUMP function to know the energy consumption anytime
Use again the JUMP function to display to display the harmonicsin
any point of the recording
HTAnalysis™ and the electrical safety
During the measures campaigns you can:
Add text and vocal comments
Add to each measure photos and videos
Customize your measurements
HT Cloud™ Share.
Whenever, whatever and wherever.
Install App HTanalysis to avail yourself of HTCloud™ database and share measurement results and recordings with your colleagues anytime and from any place on the planet.
Functions
Touchscreen colour display
Integrated WiFi connection and compatibility with HTANALYSIS App
Continuity of protective circuit with 200mA
Continuity of protective conductors with 10AWith optional accessory EQUITEST
Insulation with voltage 50, 100, 250, 500, 1000VDC
Time/Current tripping of A, AC General, Selective and Delayed RCDs up to 1000mA
Time/Current tripping of type B RCDs up to 300mA
Tripping time and current of RCDs with separate clamp jaws type B, A, AC Standard, Selective and Delayed up to 10A
Loop impedance P-N, P-P, P-PE and calculation of prospective short-circuit current
Line/Loop impedance with high resolution (with optional accessory IMP57)
Percentage voltage drop on the line
Measurement and recording of leakage currents and environment parameters
Three-phase Power quality and Energy consumption analysis:
9 types of electrical systems1Φ-2wires, 1Φ-split phase, 3Φ-3 wires, 3Φ-Aron, 3Φ-Open Δ, 3Φ-Open Y, 3Φ-2 el. 1/2, 3Φ-4 wires Y, 3Φ-High Leg.
632 parameters can be recorded for over two months
Voltage Anomalies (dips and peaks) with a resolution of 20ms@50Hz
Measurement/recording of Active, Reactive, Apparent Power
Measurement/recording of Active, Reactive, Apparent Energy
Measurement/recording of Cosphi, Power Factor
Measurement/Recording of Voltage and Current Harmonics up to 49th with THD%
• Insulation resistance measurement with test voltage up to 5kVDC
• Measurement range up to 10Tohm
• Polarization Index (P.I.) measurement
• Dielectric Absorption Ratio (D.A.R) measurement
• RS-232 interface for PC connection
• Rechargeable internal battery
• 3 system types: Single-phase, three-phase 3-wire, three-phase 4-wire. • Configurable directly from Smartphone or Tablet. • Fast trips and detailed zoom of all sizes. • Real Time. • Energy consumption logger. • 383 parameters can be displayed simultaneously. • Technology and absolute simplicity. • Harmonics Jump function.
• I-V Curve Tracer for maintenance and troubleshooting of photovoltaic systems.
• Measurement of I-V Curve of one or more modules or of one whole string up to 1500V/10A
• Measurement of open-circuit voltage and short-circuit current Voc/Isc
• Database of 30.000 selectable photovoltaic modules
• LECTRICAL SAFETY TESTING CEI 64-8
• Earth Resistance with voltammetric method with 2 or 3 points in TT, TN and IT systems
• NETWORK AND ENERGY CONSUMPTION ANALYSIS
• Measurement and recording of electrical parameters
• Voltages, Currents, Powers, Energies, cosphi, etc. in Single-phase and Three-phase systems
• Insulation with test voltage 250, 500, 1000VDC • Up to 4Gohm measurement range • Automatic discharge of device under test • LOCK feature for continuous measurements • Programmable timer up to 60s • Continuity of earth conductors with test current of 200mA • A/DC voltage up to 600V • Resistance and continuity test with buzzer
• IR Resolution 120 x 90 pxl
• Temperature range -20° ÷ 550°C
• Image frequency 50Hz
• Thermal sensitivity / NETD <0.05°C @ 30°C / 50mK
• Field of view (FOV) 50° x 37°
• ContiDC Voltage • AC TRMS Voltage • nuity test of protective conductors with 200mA • Insulation Resistance with 250, 500VDC • Trip-out time of RCDs type AC Standard • Test current selectable; 30mA, 30x5mA, 100mA, 300mA • Global Earth Resistance without RCD tripping • Global Earth Resistance with 0.1Ohm resolution
• 1500V Multifunction I-V Curve Tracer for maintenance and efficiency tests on single-phase installations.
• Measurement of efficiency of a single-phase photovoltaic system
• Measurement of I-V Curve of a module or of a string up to 1500V/10A - 1000V/15A
• Measurement of open-circuit voltage of a module or of a string (VOC) 1500V
• Measurement of short-circuit current of a module or of a string (ISC) 15A