Code: Cotel MG-50-N
Description
MG 50-N
300A max Current
250V Voltage
Single-phase test set for current or voltage
The easy to use and rugged MG 50-N is a reference for testing over and under voltage relays and also those of the Statimax ® type with no auxiliary supply.
The MG 50-N has an in-built digital measurement and control module.
The latest version has a big graphical display for easy reading of the TRMS current and control of the injection
OVERVIEW
- Light aluminium case,
- Size (W x D x H) : 390 x 300 x 310 mm.
- Weight ± 18 kg.
SPECIFICATIONS
Power supply :
- 230 Volt, 50 or 60 Hz.
Maximum power : 1500VA.
Protection :
Supply and generator by breakers.
Generator :
Single generator configurable for current or
voltage with five ranges :
50A at max. 10V
10A at max 50V
2A at max 250V
5A at max 7,5VA
1A at max 1,3A
Overload of 2 x rating for 1 minute.
DIGITAL DISPLAY
The new control enables recording of the trip time, threshold and CT ratio in an internal FLASH memory. These data can be downloaded to a computer with windows® 9x/NT/XP/2000.
The data connexions are USB and RS232.
Internal ammeter :
- 2 ranges 0-30 A and 30-300 A with automatic
selection
- Precision : 1%.
Time measurement :
- Internal START/STOP trigger
- External START.STOP trigger
- Voltage free contact or AC/DC 12 to 250 V
- precision : 0.02 % +-1ms
- range measurement : 9999.999 s
Recommended options
Options
- integrated ammeter to measure ration and direction of current transformer : MG-Aext
- Set of cables : JC06
- Software to edit test reports and records data : MCF-ACQ
Injection cables :
Réf. JC06
4 wires 2 m length sectionen 2,5 mm² with banana plug
4 test clips
2 wires length 2 m section 16 mm² with grips
1 plastic transport case. 420 x 210 x 180 mm.
More products COTEL
|
PROTECTIVE RELAY TESTING SET COTEL SMARTCASE
• 250 Aac Current Generator |
|
HIGH VOLTAGE BREAKER ANALYZER COTEL CP 4 TR
• 4 time inputs |
|
PRIMARY AND SECONDARY INJECTION CURRENT SET FOR PROTECTIVE RELAY TESTING COTEL MG 40S-N
• High current up to 300A for primary injection |
|
THREE-PHASE PROTECTIVE RELAY TESTING SET COTEL HEXAN C
• Current (25 A/ph) & Voltage (300 V/ph) |
|
PRIMARY INJECTION CURRENT GENERATOR 4000A COTEL VE 2000-N
• High current test set up to 4000 A (PCITS) |
|
THREE-PHASE PROTECTIVE RELAY TESTING SET COTEL HEXAN II
• Current (25 A/ph) & Voltage (300 V/ph) |
|
PRIMARY INJECTION CURRENT SET 1300A COTEL MCF 750-N
• High current test set up to 1300A |
|
SINGLE PHASE CURRENT GENERATOR FOR SECONDARY INJECTION COTEL MG 30-N
• 125A max Current |
|
PRIMARY INJECTION CURRENT SET 2000A COTEL VE 1200-N
• Single generator configured for current three ranges : 1A, 15A and 2000A |
|
DIGITAL TIMER FOR TESTING BREAKERS COTEL CP 1-N
• 2 Inputs voltage or dry contacts configurable(11 to 250 Vdc/ 35 to 250 Vac) |