Description
MCF 750-N Lightweight primary injection set
High current test set up to 1300A
- 2 outputs with high current 3V(1300A) et 5V(750A)
- Low ranges to inject current up to 32A
- Injection set compact and rugged
- True RMS measurement
- Voltage generator up to 250Vac
- Measurement of ratio and direction of current transformer
OVERVIEW
- Flight Case enclosure
- Dimensions : 390 x 310 x 300 mm
- Weight : 21 kg.
SPECIFICATIONS
Power supply :
- 230V 50/60 Hz
Nominal power : 750 VA.
Max power : 2.5 kVA
Protections :
- Power supply and generator by circuit breakers
and electronic control.
Generators :
One AC current generator with voltage
function depending on load.
Current generator : 5 ranges
Output 3V : 500A/5mn ; 750A/85s ; 1300A/10s
Output 5V : 300A/5mn ; 500A/38s ; 750A/8s
Output 25A with maximum voltage 24V
Output 5A/13VA
Voltage output 250V / 2A
These specifications vary as a function of the section
of the cables used, the resistance of the contacts and
the heating of the generator in the test set. Additionally,
for correct operation it is necessary to keep the
instrument on standby for a periodthat is at least as
long as the injection period.
Cables used : 2 cables length 2m section 95 mm²
DIGITAL DISPLAY
The new control enables recording of the
trip time, threshold, and CT ratio in an internal
FLASH memory. These data can be downloaded to
a computer with windows® XP/2000/VISTA. The
data connections are USB and RS232.
Internal ammeter :
- 2 ranges 0-130 A and 130-1300 A with automatic
selection
- Precision : 1%
Time measurement :
- Internal START/STOP trigger
- External START.STOP trigger
- free of voltage contact or AC/DC 12 to 250 V
- precision : 0.02 % +-1ms
- range measurement : 9999.999
Recommended options
Options
- integrated ammeter to measure ther ratio and
direction of a current transformer : MCF500-Aext
- Set of cables
- Software to edit test reports and data records : MCF-ACQ
More products COTEL
|
VOLTAGE-CURRENT SET FOR PROTECTIVE RELAY TESTING COTEL MG 50-N
• 300A max Current |
|
THREE-PHASE PROTECTIVE RELAY TESTING SET COTEL HEXAN C
• Current (25 A/ph) & Voltage (300 V/ph) |
|
SINGLE PHASE CURRENT GENERATOR FOR SECONDARY INJECTION COTEL MG 30-N
• 125A max Current |
|
PRIMARY INJECTION CURRENT GENERATOR 4000A COTEL VE 2000-N
• High current test set up to 4000 A (PCITS) |
|
HIGH VOLTAGE BREAKER ANALYZER COTEL CP 4 TR
• 4 time inputs |
|
PRIMARY AND SECONDARY INJECTION CURRENT SET FOR PROTECTIVE RELAY TESTING COTEL MG 40S-N
• High current up to 300A for primary injection |
|
PROTECTIVE RELAY TESTING SET COTEL SMARTCASE
• 250 Aac Current Generator |
|
DIGITAL TIMER FOR TESTING BREAKERS COTEL CP 1-N
• 2 Inputs voltage or dry contacts configurable(11 to 250 Vdc/ 35 to 250 Vac) |
|
PRIMARY INJECTION CURRENT SET 1300A COTEL MCF 750-N
• High current test set up to 1300A |
|
PRIMARY INJECTION CURRENT SET 2000A COTEL VE 1200-N
• Single generator configured for current three ranges : 1A, 15A and 2000A |