Code: Cotel MG 40S-N
Description
MG 40S-N Very useful for self powered relays
20A specific range for self powered or high impedance relay
300A max
- The easiest and fastest way to test self powered relays
- Specifically adpated ranges for self powered relays up to 20A for secondary injection
- Single commutator to test classical relays
- High current up to 300A for primary injectiion
- rugged and light weight conception
- True RMS measurement
OVERVIEW
- Flight case enclosure.
- Dim. L x H x P 345 x 280 x 260 mm
- Weight : 17 kg.
SPECIFICATION
Power Supply:
- 230V 50/60 Hz
Maximum power : 1200VA.
Protection :
Supply and generator by circuitbreakers
Generator :
One generator usable as a variable current or voltage generator with an output having four adapted ranges for relays with no auxiliary supply.
3A PSAA adapted
6A PSAA adapted
12A PSAA adapted
20A PSAA adapted
And 3 high current ranges
15A maximum voltage 24V ; 32A 140s
30A maximum voltage12V ; 100A 15s
70A maximum voltage 5V ; 300A 15s
DIGITAL DISPLAY
The latest controler enables recording of trip time, threshold and CT ratio in an internal
FLASH memory. These data can be downloaded to a computer with windows® 9x/NT/XP/2000.
The data connexions are USB and RS232.
Internal ammeter :
- 2 ranges0-120 A and 120-1200 A with automatic selection
- Precision : 1%
Time measurement :
- Internal START/STOP trigger
- External START.STOP trigger
- free of voltage contact or AC/DC 12 to 250 V
- precision : 0.02 % +-1ms
- range measurement : 9999.999
Recommended options
Options
- integrated ammeter to measure ratio and direction of current transformer : MG-Aext
- Set of cables : JC13
- Software to edit test reports and records data : MCF-ACQ
More products COTEL
|
PRIMARY AND SECONDARY INJECTION CURRENT SET FOR PROTECTIVE RELAY TESTING COTEL MG 40S-N
• High current up to 300A for primary injection |
|
SINGLE PHASE CURRENT GENERATOR FOR SECONDARY INJECTION COTEL MG 30-N
• 125A max Current |
|
PROTECTIVE RELAY TESTING SET COTEL SMARTCASE
• 250 Aac Current Generator |
|
THREE-PHASE PROTECTIVE RELAY TESTING SET COTEL HEXAN C
• Current (25 A/ph) & Voltage (300 V/ph) |
|
THREE-PHASE PROTECTIVE RELAY TESTING SET COTEL HEXAN II
• Current (25 A/ph) & Voltage (300 V/ph) |
|
PRIMARY INJECTION CURRENT SET 1300A COTEL MCF 750-N
• High current test set up to 1300A |
|
VOLTAGE-CURRENT SET FOR PROTECTIVE RELAY TESTING COTEL MG 50-N
• 300A max Current |
|
PRIMARY INJECTION CURRENT GENERATOR 4000A COTEL VE 2000-N
• High current test set up to 4000 A (PCITS) |
|
DIGITAL TIMER FOR TESTING BREAKERS COTEL CP 1-N
• 2 Inputs voltage or dry contacts configurable(11 to 250 Vdc/ 35 to 250 Vac) |
|
HIGH VOLTAGE BREAKER ANALYZER COTEL CP 4 TR
• 4 time inputs |