Description
The Vanguard MCCB-250 is a programmable, high-current source designed specifically for testing molded-case circuit breakers, thermal magnetic and solid-state overload motor-protection relays.
Built-in Timer
The MCCB-250’s built-in timer can test the
time-delay characteristics of protection relays
and molded-case circuit breakers. Once
the test is initiated, the current source and the
timer are automatically turned on at the next
zero-crossing point of the AC. The timer stops
when the MCCB-250 input detects a change
in the dry contact or voltage input, or detects
the removal of the test current. The test results
are then displayed in milliseconds and
fractions of cycle(s) on the unit’s back-lit LCD
screen (20 characters by 4 lines).
Current Source
The MCCB-250 has 4 current-source outputs
(5 A @ 120 Vac, 25 A @ 24 Vac, 120 A @ 6
Vac, 250 A @ 3 Vac) that conduct the test
current through the high-impedance load circuits.
Each current source can tolerate shortduration
over-loads up to 4 times the rated
current (1000 A max). This feature is used
for testing the instantaneous trip element of
molded-case circuit breakers. When using
this feature, the selected test current is displayed
on the LCD screen. When the MCCB-
250 is used as a current source, the currentfl
ow time (the current-on period) is displayed
External Current Input on the LCD screen.
The MCCB-250 also provides an external current
input (0 - 10 A). Both internal and external
current source readings can be viewed at
the same time.
Standard accessories
Part number MCCB-250 MCCB-250 and cables
Part number MCCB-250-CASE MCCB-250 shipping case
Part number MCCB-250-10FT MCCB-250 test leads - 10 foot
Part number MCCB-250-20FT MCCB-250 test leads - 20 foot
More products VANGUARD
|
DIGITAL BREAKER ANALYZER FOR CONTACT & SWITCH TIMING VANGUARD CT-7000
• dry-contact inputs: 3 channels (9021-UC) or 6 channels (9100-UC) |
|
CURRENT TRANSFORMER TEST SET VANGUARD EZCT-10
• measurement method ANSI/IEEE C57.12.90, IEC 60044-1 and ANSI/IEEE C57.13.1 |
|
MOLDED CASE CIRCUIT BREAKER TESTER VANGUARD MCCB-250
• 250 Ampere current source |
|
AUTOMATIC THREE-PHASE TRANSFORMER TURN RATIO METER VANGUARD ATRT-03A
• Capable of detecting 130 different 3-phase transformer types defined by ANSI, IEC, and Australian standards plus phase shifting transformers |
|
ON-LOAD TAP CHANGER ANALYZER AND WINDING RESISTANCE ANALYZER ON 3-PHASE TRANSFORMERS VANGUARD LTCA-40
• Auto discharge circuit for operator safety |
|
EHV HIGH VOLTAGE CIRCUIT BREAKER ANALYZER VANGUARD DIGITMR PC
• dry-contact inputs 3 dry-contact channels |
|
TRANSFORMER WINDING RESISTANCE TESTER VANGUARD TRM-40
• accurately measure resistance values from 1 micro-ohm to 500 Ohms |
|
CURRENT TRANSFORMER TEST SET TURN RATIO, EXCITATION CURVE , SATURATION GRAPHIC VANGUARD EZCT-2000C PLUS
• Performs CT excitation, current-ratio, polarity, and phase angle tests |
|
THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-03
• Highest ratio: 0.8 - 15,000 |
|
TRUE THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD TRI-PHASE
• Generates its own 3-phase transformer test voltage from single-phase AC or DC Power input |