Digital Breaker Analyzer for contact & switch timing Vanguard CT-3500

Code: Vanguard CT-3500


 

Datasheet PDF, 0.65 Mb
   

Description

  • Dry-contact inputs: 3 channels
  • Trigger input voltage open/close: 30 ¬ 300 V, DC or peak AC
  • Breaker operations: Open, Close, Open-Close, Close-Open
  • Timing resolution: ±0.1 millisecond
  • Detect Main & Insertion Resistor Contacts on same input
  • USB computer interface
  • USB Flash drive interface (Flash drive not included)
  • Store 128 test records internally
  • Initiate Breaker Operation
  • Built-in 2.5" wide Thermal Printer
  • Rugged "QWERTY" style membrane keypad

 

The CT-3500 S2 is Vanguard’s second generation, stand-alone, digital, microprocessorcontrolled, circuit-breaker timer. It measures the elapsed time from the instant a breaker coil is energized to the instant of opening or closing of a circuit-breaker’s dry contacts. In addition to timing a breaker’s contact response time, the CT-3500 S2 can also time relays or other switching functions that use an initiating trigger voltage (30- 300 Volts DC or AC). The timer-triggering voltage starts three independent electronic timers. Each timer is individually stopped by its respective dry-contact closing or opening.

The CT-3500 can fully analyze the timing of all circuit breaker operations (Open, Close, Open - Close, and Close - Open). Timing results are displayed in milli-seconds and cycles on the unit’s back-lit LCD screen and can be printed on the built-in 2.5-inch wide thermal printer.

 

Contact Timing Inputs

The CT-3500 S2 features three dry-contact, timer-channel monitoring inputs. The dry-contact

channel power supply is fuse-protected. All inputs are shunted to ground until the instant a test is initiated. All contact timing inputs are protected against static discharge. A contact self-test cable-mode is also available for testing cables or connections to the breaker.

 

Internal Test Record Storage

The CT-3500 S2 can store up to 128 test records in Flash EEPROM. Test records can be retrieved and printed on the built-in thermal printer, or they can be transferred to a PC via the unit’s USB interface. The USB interface can also be used for diagnostic testing and for updating firmware.

The CT-3500 S2 also features a USB Flash drive interface that can be used to store test records on an external USB Flash drive.

A Windows®-based Circuit Breaker Analysis application is provided with each unit and can be

used to transfer test records to a PC. Test records can also be reviewed, printed or exported in Excel, PDF, and XML formats for further analysis

 

User Interface

The CT-3500 S2 features a back-lit LCD screen (128 x 64 pixels) that is viewable in both bright sunlight and low-light levels. A rugged, 44-key, "QWERTY" membrane keypad is used to control the unit and input data. The unit's built-in 2.5- inch wide thermal printer can be used to print test reports.

 

 

More products VANGUARD

600A AC PRIMARY CURRENT INJECTION SOURCE FOR RELAY TESTING VANGUARD PCI-600

• Results displayed on a 4-line by 20-character backlit LCD
• Test currents from 10 to 600 amperes AC
• Also has an external-current input (0-10 A)
• timer reading range 1 m.. 2 hours

 

DIGITAL BREAKER ANALYZER FOR CONTACT & SWITCH TIMING VANGUARD CT-3500

• Dry-contact inputs: 3 channels
• Trigger input voltage open/close: 30 ¬ 300 V, DC or peak AC
• Breaker operations: Open, Close, Open-Close, Close-Open
• Timing resolution: ±0.1 millisecond
• Detect Main & Insertion Resistor Contacts on same input
• USB computer interface
• Built-in 2.5" wide Thermal Printer

 

THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-03

• Highest ratio: 0.8 - 15,000
• Built-in 4.5" thermal printer
• Excitation current measuring
• Phase angle measuring
• Computer interface
• Name-plate turns ratio calculation
• Computed % error based on measured and calculated ratio

 

CURRENT TRANSFORMER TEST SET TURN RATIO, EXCITATION, SATURATION, POLARITY VANGUARD EZCT-2000A

• Perform Saturation, Ratio and Polarity Tests
• Perform CT Winding Resistance Test
• Fully Automated
• Test record header information including company, substation name, circuit ID, manufacturer, CT serial number, operator name, and test record-comments
• Plot Multiple Saturation Curves
• Store 140 Records (of 10 Saturation Curves)
• Computer Interface
• USB Flash drive interface

 

DC CIRCUIT BREAKER CONTACT LOW RESISTANCE MICROOHMMETER 200A VANGUARD DMOM-200 S3

• 1 to 200A programmable test current
• Resitance range: 1µ?..10m? at 200A to 1µ?..5? at 1A
• Very lightweight: 19.8 lbs. (8.9 Kg)
• Measures circuit breaker contact resistance with safety ground on (with the Dual Ground option)
• Stores test records on-board or on external USB Flash drive
• Built-in 2.5" wide thermal printer

 

PORTABLE RELAY TEST SET VANGUARD RFD-200

• Timer: 0 to 9.999 sec, 1 ms resolution; 10.00 to 99.99 sec, 10 ms resolution, 100.00 to 999.999 sec, 100 ms resolution
• built-in Timer displays contact time in both cycles and milliseconds
• AC current source with 3 outputs (10A, 40A, 100A)
• AC voltage source for testing relays up to 250 Vac
• DC Voltage source (0 - 300 Vdc)
• Volt meter input (0 - 600 V input range)
• Three power supplies (24 Vdc, 48 Vdc, 124 Vdc)
• Built-in power resistors

 

DIGITAL BREAKER ANALYZER FOR CONTACT & SWITCH TIMING VANGUARD CT-7000

• dry-contact inputs: 3 channels (9021-UC) or 6 channels (9100-UC)
• timing windows: 1 second, 10 seconds, or 20 seconds
• timing resolutions ±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milli-seconds @ 20 sec. duration
• breaker operations: Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
• Fully analyze circuit breaker's performance
• measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
• USB computer interface
• USB Flash drive interface (Flash drive not included)
• Built-in 4.5" wide Thermal Printer

 

TRANSOFORMER BREAKER CONTACT RESISTANCE MICRO OHM METER 600A VANGUARD DMOM-600

• 10 to 600A programmable test current
• Resitance range: 1.5m? at 600A to 450m? at 10A
• Measures circuit breaker contact resistance with safety ground on (with the Dual Ground option)
• Stores test records on-board or on external USB Flash drive
• Built-in 2.5" wide thermal printer

 

MOLDED CASE CIRCUIT BREAKER TESTER VANGUARD MCCB-250

• 250 Ampere current source
• 4 current-source outputs (i.e., 5 A @ 120 Vac, 25 A @ 24 Vac, 120 A @ 6 Vac, 250 A @ 3 Vac)
• 4-line by 20-character LCD display
• Provides external current input (0-10 A)

 

CURRENT TRANSFORMER TEST SET VANGUARD EZCT-10

• measurement method ANSI/IEEE C57.12.90, IEC 60044-1 and ANSI/IEEE C57.13.1
• output test voltages 0..50 Vac @ 10A max; 0 - 200 Vac @ 10A max; 0 - 1200 Vac @ 1.5A max (5 min on, 10 min off)
• voltage reading range 0..1,250 Vac
• current ratio range 0.8..99: ±0.5%, 100..999: ±1.0%, 1,000..5,000: ±2%
• phase angle measurement 0..360 degrees
• Perform Saturation, Ratio and Polarity Tests
• Fully Automated
• Comprehensive Graphic and Tabulated Test Reports
• Plot Multiple Saturation Curves
• Computer Interface & pc software