HIGHTEST SUWI-120 Multifunction Substation Tester

Code: SUWI-120 SUWI120 CABINET SUBSTATION


 

Datasheet PDF, 1.34 Mb
 

Description

HIGHLIGHTS

  • Multifunctional test device
  • Relay Timing Tests
  • Turns Ratio Tests
  • Contact Resistance Tests
  • 3ph Circuit Breaker Timing Tests

SUWI-120 series stands as a versatile testing instrument meticulously crafted to evaluate the performance of power and control apparatus within substations. It encompasses an array of essential tests, including the precise assessment of Relay Timing, the determination of a Transformers Turns Ratio, the scrutiny of Circuit Breaker Contact Resistance and Timing, as well as the examination of MCBs, among other critical functions. This all-encompassing substation testing device has earned the name SUWI, from our belief in its skills as a Substation Wizard.

RELAY TIMING MEASUREMENT

The SUWI instrument can automatically test over-current, over-voltage, directional overcurrent relays and frequency control relays. SUWI has an adjustable output current up to 110A AC / 120A DC and an adjustable output voltage to 150V AC / 220V DC. It has four universal input modules.

TURNS RATIO MEASUREMENT

Employing elements of performance tests specified in the ANSI/IEEE C57.12.90 standard, the instrument performs transformer ratio measurements to a precision of 0.08 % across a ratio range of 0.8 to 10,000. SUWI also measures phase angle and polarity, and it can generate 1V, 4V, 10V, 40V and 100V AC test voltages to facilitate the measurement of turns ratio for current, voltage and power transformers.

CONTACT RESISTANCE / LOW RESISTANCE MEASUREMENT

SUWI has an adjustable output DC current up to 120 Amps which facilitates the measurement of contact resistance of a circuit breaker, a shunt or disconnector. SUWI-120 can measure resistance up to 5 Ohm, with a resolution of 0.01uOhm.

CIRCUIT BREAKER TIMING

Contact Timing Tests are performed to determine a breakers contact performance against its manufactured specifications. The timing for a breakers operation such as OPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN and OPEN-CLOSE-OPEN are measured for all three-phases simultaneously. SUWI can perform 3-phase circuit breaker timing test cycles as described above along with coil current measurements using internal and external trigger inputs.

TECHNICAL SPECIFICATIONS

Measurement ParametersRelay Timing Tests (over current relays, over voltage relays, directional over current relays, frequency control relays);
Turns Ratio Measurement, Phase Angle, Polarity, Ratio Error (%);
Contact Resistance/Low Resistance Tests (Circuit breaker contact resistance and shunt resistance)
Circuit breaker timing test (3-phase circuit breaker timing tests; open, close, open-close, close-open, open-close-open timings, coil current measurement, internal and external trigger operations)

PROTECTION RELAY TIMING MEASUREMENT FEATURES
Current OutputsUp To 110 A AC (magnitude and frequency adjustable)
Up to 120 A DC
Voltage Outputs150 V AC (magnitude and frequency adjustable)
220 V DC
Universal Input Modules4 input module; Binary wet/dry
Up to 300 V AC/DC voltage measurement

TURNS RATIO MEASUREMENT FEATURES
Ratio Measurement ModesCT Mode
PT Mode (Single-Phase and Three-Phase)
Test VoltagesCT Mode: 1 V and 4 V ;
PT Mode: 1, 4, 10, 40 & 100 V
Ratio Range0.8 -10,000

CONTACT RESISTANCE/LOW RESISTANCE MEASUREMENT FEATURES
Measurement ModesStatic Resistance Measurement
Auto Test ModeYes
Test CurrentUp to 120 A DC
Measurement RangeUp to 5 Ohm

CIRCUIT BREAKER TIMING MEASUREMENT FEATURES
Measurement ParametersContact Timing (O, C, O-C, C-O & O-C-O); Coil Current Measurement, Internal and External Trigger Operations
Timing Windows1s, 10s, 20s
Timing Accuracy0.05% rdg ± 0.1 ms
Contact detectionYes
Trigger input voltage 24 300 V DC or ACpeak
Breaker Initiate Capacity20 A, 300 V DC or ACpeak
Initiate current reading range 0 20A DC, 5 kHz
GENERAL FEATURES
Power Supply100-240 V, 47/63 Hz,
Internal MemoryYes
CommunicationUSB 2.0/1.1 Standard-B, Ethernet
PC SoftwareDMP Software
Display7-inch IPS 1024*600 pixel touch panel display
Dimensions  (429 x 328 x 236) mm
Weight10.70 kg
TemperatureWorking : -10 °C to +60 °C; Storage: -30 °C to +70 °C
Humidity95% RH Non-condensing
Protection ClassIP67 (case lid closed)

 

Standard accessories

Included in the Package5x5m Input Cables (Red), 5x 5m Input Cables (Black), 2x 3m Contact Cable (White), 2x 3m Contact Cable (Blue), 1x 2.5m Current Cable (Red), 1x 2.5m Current Cable (Black), Power Cable, Ground Cable, USB Cable, Ethernet Cable, USB flash drive, Instruction Manual (Soft Copy), DMP Software, Cable Bag

 

Recommended options

Optional5m Measurement Cable Set for TURA-01 , TURA01 Cable Set Adapter, CIBREL3 Cable Set Adapter, 6m Contact Cable Set of contact 1 , 2 &3
 

More products HIGHTEST

HIGHTEST CBSM

• Contact timing channels 6 contact timing channels; Accuracy: 0.01 ms
• CT timing channel 1 CT timing channel, 500 mA, Accuracy: +-0.5 ms
• Digital transducer channels 3 digital transducer channels; Accuracy: 0.02
• V1 voltage channel 20 Vrms
• V2 voltage channel 30 Vdc
• Internal trigger channel 2 A
• External trigger channel 24 Vdc

 

HIGHTEST TRCAL-10K TURN RATIO METER CALIBRATOR

• Ratio Range 1 to 10,000 (1:1, 2:1, 5:1, 10:1, 50:1, 100:1, 200:1, 500:1, 1,000:1, 2,000:1, 5,000:1, 10,000:1)
• Exciting Voltage Range 1 V -250 V
• Exciting Windings H1-H2 Windings

 

HIGHTEST TURA-01 TRANSFORMER TURN RATIO TESTER

• Turns Ratio Measurement (Single-phase and three-phase measurement)
• Ranges from 0.8 to 33,000 Ratio Measurement
• High Accuracy (0.08 %)
• 1V, 4V, 10V, 40 V and 100 V AC Test Voltages

 

HIGHTEST CIBRE-L6 CIRCUIT BREAKER ANLAYZER

• Contact Timing (O, C, O-C, C-O & O-C-O)
• 6 Dry Contact Inputs
• Timing Accuracy: 0.05% rdg ± 0.1 ms
• Timing Windows: 1s, 10s & 20s
• 2.25” Built-in Printer
• 4.3” TFT Touch Colour Display

 

HIGHTEST PICU-1000 PRIMARY INJECTION CURENT SET 1000A

• High Current Capability Continuous output up to 1000A for primary injection applications.
• Multi-Purpose Testing Suitable for testing Protective Relays, MCCBs (Moulded Case Circuit Breakers), and CT Turns Ratio.
• Accurate & Reliable Provides precise measurement of current and operating time.
• Rugged & Portable

 

HIGHTEST TRIORES-20 TRANSFORMER WINDING RESISTANCE TESTER

• Fully Automatic Three-phase and single-phase resistance measurement with three-phase cable configuration
• Measurement range, 0.1 uOhm to 100,000 Ohm
• 0.001 A to 20 A DC adjustable current output
• High accuracy (0.1%)
• Test Voltage 50 V
• Demagnetisation feature

 

HIGHTEST TURA-03 TURN RATION TRANSFORMER TESTER TTR

• Turns Ratio Measurement (Single-phase and three-phase measurement)
• Ranges from 0.8 to 50,000 ratio measurement
• High Accuracy (0.08 %)
• 1V, 4V, 10V, 40V, 100V and 250V AC test voltages

 

HIGHTEST ARES-200D 200A LOW CONTACT RESISTANCE WITH DYNAMIC AND STATIC RESISTANCE MEASUREMENT

• ontact resistance measurement
• Adjustable current: 1 A to 200 A
• Measurement range from 0.1 µOhm to 5 Ohm
• Typical accuracy 0.1%
• Static resistance measurement
• Dynamic resistance measurement
• Dual ground test mode

 

HIGHTEST CIBRE-60 6-CONTACT TIMING CIRCUIT BREAKER ANALYSERS

• Contact Timing (O, C, O-C, C-O and O-C-O)
• Motion Tests (Transducer Speed, Stroke, Bounce)
• 6 Dry Contact Inputs
• Timing Accuracy: 0.05% rdg ± 0.1 ms
• Timing Windows: 1s, 10s & 20s
• 7TFT Touch Colour Display

 

HIGHTEST VABO-80 VACUUM BOTTLE TESTER FOR TESTING CIRCUIT-BREAKER VACUUM INTERRUPTER

• Circuit Breaker Vacuum Bottle Interrupter Testing
• Electrical Safety Gloves Integrity Test
• Automatic Testing
• 10 kV to 80 kV DC with 1 kV step voltages
• High Accuracy (1.5 %)
• 100 μA, 200 μA and 300 μA leakage current preset value