Vacuum Bottle Tester for High Voltage Circuit Breaker test Vanguard VBT-60

Code: Vanguard VBT-60 / VBT-80


 

Datasheet PDF, 0.42 Mb
   

Description

  • Automatic Testing
  • 10 kV to 60 kV DC output in 5 kV steps
  • Selectable dwell time from 5 seconds to 2 minutes
  • Digital voltage and current display
  • Failure indicator lamp
  • Very light-weight

 

VBT-60/VBT-80

vacuum bottle testers

The VBT-60 and VBT-80 are microprocessor-based, portable, dc (60 kV and 80

kV, respectively) vacuum bottle testers. These lightweight, portable testers are

designed for testing circuit-breaker vacuum bottles in the fi eld and at the shop.

Test voltages can be selected from 10 kV dc to 60 kV dc in 5 kV steps for the

VBT-60 and from 10 kV to 80 kV dc in 5 kV steps for the VBT-80. The high-voltage

test time can be set from 5 seconds to 2 minutes. The test voltage is raised

to the selected voltage and held for the test time duration. After the test time

duration has elapsed and the leakage current did not pass the preset value of

100 µA, 200 µA, or 300 µA, the test voltage is returned to zero. If a fl ash-over

condition occurs, such as bottle failure, the test voltage is immediately turned

off, a "Failure" message is displayed on the LCD screen, and the "TEST FAIL" LED

light on the unit is also illuminated.

The presence of high voltage is indicated by an audible tone and an illuminated

"HIGH VOLTAGE" LED light. For additional operator safety, an "ARM" switch

must be held down during testing.

The VBT-60 and VBT-80 feature a back-lit LCD screen (16 characters by 2 lines)

that is viewable in both bright sunlight and low-light levels. A turn-and-press

knob is used to control the unit. An RS-232C interface port is provided for factory

calibration and diagnostic testing.

Each unit is furnished with a 10-foot test cable that is terminated with a quickdisconnect

test clip. A transportation case is also included.

 

Standard accessories

Part number VBT-60 VBT-60 and cables

Part number VBT-80 VBT-80 and cables

Part number VBT-HV-CABLE Hight Voltage Cable

 

More products VANGUARD

TRUE THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD TRI-PHASE

• Generates its own 3-phase transformer test voltage from single-phase AC or DC Power input
• Capable of detecting 130 different 3-phase transformer types defined by ANSI, IEC,
• 64 x 128 graphic LCD screen
• Store up to 128 transformer test-plans in Flash EEPROM
• Store up to 112 test records in Flash EEPROM
• Built-in USB Flash Drive Interface
• Computer Interface (RS-232C and USB Port)
• 4.5 Inch thermal printer
• Built-in transformer load tap changer

 

TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20

• accurately measure resistance values from 1 micro-ohm to 2,000 Ohms
• Auto-discharge circuit for operator safety
• Demagnetizes transformer after test
• Selectable test current from 1A to 20A
• RS-232C, USB, and Bluetooth computer interfaces
• Built-in thermal printer

 

10A AC/DC CURENT POWER SOURCE FOR TESTING CIRCUIT BREAKERS AND PROTECTIVE RELAYS VANGUARD UPS-S2

• Isolated variable 1-300 Vdc source
• Isolated variable 1-240 Vac source
• 10 ampere continuous current

 

TRANSOFORMER BREAKER CONTACT RESISTANCE MICRO OHM METER 600A VANGUARD DMOM-600

• 10 to 600A programmable test current
• Resitance range: 1.5m? at 600A to 450m? at 10A
• Measures circuit breaker contact resistance with safety ground on (with the Dual Ground option)
• Stores test records on-board or on external USB Flash drive
• Built-in 2.5" wide thermal printer

 

DC AUTOMATIC CIRCUIT BREAKER CONTACT RESISTANCE MICRO-OHMMETER 200A VANGUARD AUTO-OHM 200 S3

• 1 to 200A programmable test current
• Resitance range: 1µ?..10m? at 200A to 1µ?..5? at 1A
• Very lightweight: 16.8 lbs. (7.6 Kg)
• Measures circuit breaker contact resistance with safety ground on (with the Dual Ground option)
• Stores test records on-board or on external USB Flash drive
• Rugged, 44-key "QWERTY" membrane keypad
• Windows XP/Vista/7 Analysis Software (included with purchase)

 

VACUUM BOTTLE TESTER FOR HIGH VOLTAGE CIRCUIT BREAKER TEST VANGUARD VBT-60

• Automatic Testing
• 10 kV to 60 / 80 kV DC output in 5 kV steps
• Selectable dwell time from 5 seconds to 2 minutes
• Digital voltage and current display
• Failure indicator lamp
• Very light-weight

 

THREE-PHASE TRANSFORMER TURN RATIO TESTER VANGUARD ATRT-03

• Highest ratio: 0.8 - 15,000
• Built-in 4.5" thermal printer
• Excitation current measuring
• Phase angle measuring
• Computer interface
• Name-plate turns ratio calculation
• Computed % error based on measured and calculated ratio

 

CAPACITIVE VOLTAGE TRANSFORMER TURN RATIO TESTER VANGUARD CVT-765

• Standalone or computer-controlled
• Can test CVT's rated up to 765 KV
• Displays turns-ratios from 75-15,000
• Calculates turns-ratio percentage error when nameplate voltages are provided

 

CURRENT TRANSFORMER TEST SET TURN RATIO, EXCITATION, SATURATION, POLARITY VANGUARD EZCT-2000A

• Perform Saturation, Ratio and Polarity Tests
• Perform CT Winding Resistance Test
• Fully Automated
• Test record header information including company, substation name, circuit ID, manufacturer, CT serial number, operator name, and test record-comments
• Plot Multiple Saturation Curves
• Store 140 Records (of 10 Saturation Curves)
• Computer Interface
• USB Flash drive interface

 

THREE-PHASE TRANSFORMER WINDING RESISTANCE METER VANGUARD TRM-20

• accurately measure resistance from 1 micro-ohm to 500 Ohms
• Perform three phase test on a transformer without the need to switch cables
• Can provide individual Delta winding resistance values
• Can provide individual Wye (with no neutral) winding resistance values
• Demagnetize transformer after test
• Selectable test current from 1A to 40A
• Computer control via RS-232C, USB, or Bluetooth interface
• Built-in 2.5" wide thermal printer