Cod: Applied Precision HWR
Descriere
Half Wave Rectifier
Direct current and even harmonics test unit
Half Wave Rectifier is designed for meter testing according to IEC 62053-21 Appendix A.1 - Half wave rectification (d. c. and even harmonics).
The Half Wave Rectifier HWR 1x12B is a single phase (HWR 1112B) and three phase (HWR 1312B) device which acts as an ideal diode with null-voltage switch and negligible power loss. The device enables to test single or three-phase meters up to 120A. It requires division of tested meters into two equal sections. The sections are fed by the opposite half-wave. Due to null-voltage switch principle the symmetry of the load impedance is not critical for exact power split and therefore for the measurement accuracy. The Half Wave Rectifier acts as a linear device and does not affect the current source signal distortion.
Half Wave Rectifier has two modes of operation:
Half Wave mode
The input current is split - the negative half wave flows through the Section 1 and the positive half wave flows through the Section 2
Normal mode (Half Wave Disabled)
Both sections are connected in series and the input current flows through both sections
Models
|
Model |
Phases |
|
HWR 1112B |
1 |
|
HWR 1312B |
3 |
Alte produse APPLIED PRECISION
|
STANDARD REFERINTA FAZA ZERO APPLIED PRECISION ZPS 1101
• Broad-band operation up to 100th harmonic of mains frequency |
|
RECTIFICATOR UNDA CURENT DIRECT TESTARE CONTOARE ELECTRCITATE APPLIED PRECISION HWR
• Ideal zero-voltage switch |
|
STANDARD REFERINTA CLASA 0.05 0.02 0.01 CALIBRARE CONTOARE ELECTRICE APPLIED PRECISION RS 2X30
• Single-phase and three-phase versions in classes 0.05, 0.02, 0.01 |
|
SURSA TRIFAZATA SARCINA FANTOMA CU CONTOR ETALON INTEGRAT PT CALIBRARE CONTOARE ELECTRICE
• Multifunction portable signal source with integrated working standard of power and energy |
|
SONDE DE CURENT AC FLEXIBILE ROGOWSKI APPLIED PRECISION SYMMPROFLEX
• Accuracy up to 0.2 % in amplitude and 0.1 ° in phase |
|
TRANSFORMATOR DE PRECIZIE TENSIUNE SECUNDAR IZOLAT MONOFAZAT APPLIED PRECISION D-MSVT 1110B
• DIN rail mounting possibility |
|
TRANSFORMATOR CURENT REJECTOR MOD COMUN TESTARE CONTOARE ELECTRICITATE APPLIED PRECISION CMRI
• Standalone through-hole precision electronically compensated transformer with single |
|
ANALIZOR PORTABIL PROPRIETATI TRANSFER CALDURA APPLIED PRECISION ISOMET 2114
• Measurement of Thermal Conductivity, Thermal Diffusivity, Volume Heat Capacity and Temperature |
|
STAND AUTOMATIZAT MASURA, TESTARE, CALIBRARE CONTOARE ELECTRICITATE APPLIED PRECISION ELMA
• The accuracy of the power and energy reference meter is available up to 0.01 %. The reference meter measures all main and influencing quantities inclusive harmonic analysis and distortion of the test signals. |
|
SOFTWARE GESTIONARE DATE SISTEME AUTOMATE MASURA SI TESTARE CONTOARE ELECTRICITATE APPLIED PRECISION ELMA
• User friendly programs for Microsoft Windows. |